    Specification:
    1) Sensing input
    - Voltage: 240 V AC ±10% for 1 phase, 380 V up to 480 V AC ±10% for 3 phase, 2 line sensing AVR Senses true average of the line to line waveform. Use Resistor (SMD) network for trouble free sensing & control of sensed voltage / regulation.
    2) Input power
    - Voltage: 415V for 3 phase and 240V for 1 phase
    - Frequency: 50/60 Hz
    3) Output power
    - Voltage: 105 V DC at 240V AC Input
    - Current:
    • 6 Amps DC Continuous
    • 8 Amps for 30sec. (when allowed by field resistance)
    4) Operating temperature: -20ºC to +70ºC
    5) Storage temperature: -40ºC to +80ºC
    6) Voltage adjustment: min ± 10% of rated voltage.
    7) Stability adjustment: adjustable to get Steady state Stability good transient response.
    8) Remote Voltage adjustment: to get ±10% of set terminal voltage (with 2W / 2.5W , 1 Watt pot).
    9) Droop for parallel operation: 4% droop for 5 Amps from «U» phase.
    10) Auxiliary input A1 & A2: ±4.5V DC will give change in terminal voltage by ±10%.
    11) Under frequency roll - off adjustment: available below 46 Hz for 50 Hz & below 56 Hz for 60 Hz.
    12) Voltage Build up: ≥ 2 Volts (L-N)
    13) Voltage regulation: ± 0.8% at AVR terminals.
    14) Thermal drift: ± 1% for 30º C change in temperature.
    15) Response time: less than 50 milli seconds.
    16) Closed loop response: typically 0.5sec to recover to 98% of the set voltage for a field forcing ratio of 1:2.
    17) Sense Loss protection: voltage should collapse, when the sensing circuit is open.
    18) Over excitation protection: 10V DC to 85V DC. Set point : 60 V DC
    19) Fuse for protection: 6 Amps, 240 Volts AC.
    20) All potentiometers: multi-turn except Droop pot (Droop-single turn)
    21) Sealing of Potentiometers: except V – trim pot all pots are sealed.
    22) Frequency roll off indicator: LED provided (UF).
    23) Sense Loss indicator: LED provided (SL).
    24) Over excitation indicator: LED provided (OE).
    25) Protection on the devices: Suitable R-C Snubber to be provided for the device used to protect this from surge.
    26) Potting/ Encapsulation Details: the components on the AVR should be completely encapsulated with suitable PU resin compound to absorb transients / vibrations while in operation.
    27) Excitation details of alternator: (typical)
    - Full load:
    • Excitation Voltage: 40 to 50 Volts
    • Excitation Current: 2.5 to 5.0 Amps
    28) Terminal marking: refer drawing
    29) AVR Testing: Burn in test, Thermal cycling, Static test, Voltage variation check, Build up test, FRO check, Stability check, QDC check, Remote voltage check, DC input voltage check.