Basler Voltage Regulator AVR AVC110-6 for Generator Genset
Part Number:
AVC110-6,AVC1106
See Details:
DC OUTPUT POWER:
6 Adc at 110 Vdc maximum
continuous, 10 Adc at 200 Vdc 10 seconds forcing.
(Forcing with 240 Vac nominal input).
EXCITER FIELD DC RESISTANCE:
18.3 ohms
minimum; 100 ohms maximum.
AC POWER INPUT:
Operating range: 180-277 Vac
single phase, 50/60 Hz or 125Hz PMG ±10%. Burden
800VA.
SENSING INPUT:
342-528 Vac single phase, 50/60 Hz
±10% <5VA.
VOLTAGE ADJUST RANGE:
342-528 Vac.
REGULATION ACCURACY:
Better than ±0.5% no
load to full load.
RESPONSE TIME:
Less than 1.5 cycles for ±5%
change in sensing voltage.
EMI SUPPRESSION:
Internal electromagnetic
interference filtering.
PARALLEL COMPENSATION:
5A <10VA. Adjustable
up to 6% droop for 0.8PF.
ACCESSORY INPUT:
±3Vdc signal causes a ±30%
change in the regulation set point.
OVEREXCITATION SHUTDOWN:
Field voltage shuts
down after time delay if exciter field voltage exceeds a
set point adjustable approx. 75-125Vdc. The time delay
is inversely proportional to the magnitude of the de-
tected overvoltage condition up to the 240 Vdc point,
thus allowing nominal forcing for approximately 10
seconds. Beyond 240 Vdc, the field voltage is removed
instantaneously.
VOLTAGE BUILDUP:
Internal provisions for automatic
voltage buildup from generator residual voltages as low
as 5 Vac.
TERMINATIONS:
Screw type.
POWER DISSIPATION:
35 Watts maximum.
OPERATING TEMPERATURE:
-40°C (-40°F) to +60°C
(+140°F).
STORAGE TEMPERATURE:
-40°C (-40°F) to +70°C
(+158°F).
VIBRATION:
Withstands 1.5 Gs at 5 to 29 Hz; 0.036”
double amplitude at 29 to 52 Hz; and 5 Gs at 52 to 500 Hz.
SHOCK:
Withstands up to15 Gs in each of three
mutually perpendicular axes.